Choosing A Motor
By: Dr. J.C. Compter
Professor of Engineering at Eindhover University
This article is a short extract of "choosing a motors" the rest of the article will be published in
the next issue of Mavilor Express.
The process of choosing a motor is preceded by an analysis of the load; this analysis must atleast provide an answer to:
1) maximum speed
2) maximum torque required
3) the period of time of the motor torque
4) in combination with a transmission 1 :n Y/N
A standpoint must also be taken as regards:
1) Main emphasis on operational reliability or performance
2) Is the cost price important and if so, what then is the budget for the complete drive, consisting of the transducers, amplifier, motor
and any transmission?
3) Standardization
4) Preference for a brand
5) Space restrictions
6) Requirements of motor temperature and the environment
7) Weight restrictions
8) Preference for a particular type of servomotor
9) A protection class desirable (splashproof, explosion-proof.)
10) Reliability and life
11) Imbalance vibrations, cogging, noise, electromagnetic radiation
12) Requirements of the bearings
13) Mounting on a frame by means of a flange, screw thread, etc.
14) Method of connection, integral temperature sensor.
These points are not listed in any particular order; their priority is usually determined by the application. Following this preparatory
work, we can look at different motors.
Analyzing the applicability of a motor is generally a time-consuming process; a number of suppliers have therefore developed software that can
present realistic choices on the basis of a database and a questionnaire. The Motsel program is one such example. We shall now consider
the criteria employed in software of this kind.
Torque, speed and the area of activity
As we have previously indicated, a motor is characterised
by a torque-speed relationship (see Fig. 6.1).
Remember that this relationship goes with a particular motor
temperature, because the motor resistance and K-factor are temperature-dependent.
The purpose of a motor is the delivery of mechanical power
; this power is given by :
With
it is easy to establish that the maximum power Popt is delivered
at :
and then is equal to :
Fig.
6.2 shows the curve of the output power as a function of the torque.
The interpretation of this figure requires some explanation. Let's
say that the motor sets itself to the speed indicated under the
influence of the load. A certain motor torque goes with it (readable
via the horizontal line). Finally, an output power Pout goes with
this torque. The efficiency of the drive is also a factor. If
we include both a static friction Tf and a viscous friction Td
=wd, then we have:
Following substitution we have:
with Ts the stall torque.
As shown in Fig. 6.3, a point on the torque-speed curve T-n
can therefore be indicated where the motor has maximum efficiency.
By way of substitutions and differentiation of the efficiency
to the torque T we can prove that a maximum efficiency Pshaft/Pin
is obtained at:
and
in choosing a motor we have to find a compromise between efficiency
and output power. Giving priority to efficiency leads to a larger
motor. In Fig. 6.3 a good compromise can usually be found inside
the range given by the two points marked on the maximum torque-speed
curve and the origin.
In a servo system however the motor voltage is not fixed;
the controller will supply the motor with a varying voltage by
way of the output amplifier. Fig. 6.4 shows along which lines
the points Popt and nopt move.
Given the aforementioned compromise, the motor working point
will preferably lie between the line of maximum efficiency and
output in Fig. 6.4.
Combining Fig. 6.4 with Fig. 3.12 gives us Fig. 6.5. SOA stands
for Safe Operation Area preferably operate between the Popt and
Hopt line to combine an acceptable efficiency and a high output
power. Additionally one has to reconsider the motor chosen when
the worst case operation point can be found under the T-w line
belonging to 0.5 Unom (motor under loading). Within Philips on
also prevents to exceed momentarily the T25-line; this is based
on a questionable carefulness; the more one knows concerning the
application and motor one can shift this limitation upwards. Finally
remains the area with a dashed contour as preferred operation
area.
Steepness
Here we define the steepness of a motor as K*K/R. This is
one of the most important motor parameters, because it can be
found in the equations:
* Dissipation
* Mechanical time constant
* Speed versus torque
* Maximum continuous torque
*the position of maximum efficiency
When the terminals of a motor are short circuited one will
notice that the motor acts as a viscous brake with S as the ratio
between the torque and radial speed (prove this).
For servo technology a high value of S is attractive, because
it leads to less dissipation at a given torque, a lower mechanical
time constant, a higher permissible torque.
Load Cases
Static Load
If the servo loop has the task of driving load at an almost
constant torque and speed (a static load), it is easy to show
in fig. 6.4 where the working point of the motor is. Verification
of the maximum permissible value of the torque and the speed is
followed by check on Trms, which must be less than T100.
And if the point Trms/ nominal speed is also between the lines
of Popt and çopt, then we have a suitable motor. If this is not
the case, a transmission can provide a solution. Let's say that
we have the working point 1 in Fig. 6.6. For the mechanical power
we have Pout=ùload.Tload.A transmission (without losses) with
a transmission ratio i leads to Tmotor= ùload/i. The result is
that, depending on the value of i, a different point on the curvein
Fig. 6.6 can be used. With static loads we have complete freedom
to choose such a transmission ratio that the efficiency for example
is at a maximum or it is possible for example to suffice with
a(n) (available) supply voltage.
Dynamic Load
Contrasting with this static load is the pure dynamic load,
which is characterised by a load torque that is only used for
the constant acceleration and deceleration of the load and motor.
This means that the moments of inertia of load and motor in combination
with the desired accelerations determine the motor torque required.
With a transmission ratio i, the torque required is as follows :
The transmission ratio i largely determines what torque the
motor must deliver. Since the cost price of a motor and the maximum
torque are closely linked, a low torque is preferable. The question
now is what transmission ratio i must be chosen in order that
a minimum torque T suffices. Depending on the load, the curve
of the motor torque as a function of the transmission ratio can
be a flat or a strong minimum (see Fig.
6.7). Differentiation of the above equation to ùmotor leads
to the condition that is known as ¨INERTIAL MATCH¨.
With i =wmotor/wmotor gives us:
The solution is:
The fact that there is a minimum can be explained as follows:
if an extremely large transmission ratio i is
chosen, the term in equation (105) with the moment of intertia
of the load will predominate and the torque will grow proportionately
to i. This leads to an initial conclusion: reduce i. If this were
to go too far, then the term in the formula with the motor moment
of inertia would predominate. The reason is that with a low i
the angular velocity of the motor is
high, so that a lot of energy has to be expended on the acceleration/deceleration
of the motor. The curve of the motor torque as a function of i
is an hyperbola ( : l/i) at low values
of i, which leads to the conclusion : increase i. Result somewhere there is an optimum. Show that
the motor sees as load torque T:
The procedure to follow to see whether a particular motor
is suitable for this dynamic load:
1) Determine the transmission ratio that goes with the ¨Inertial
Match¨.
2) Process the moment of inertia of a suitable transmission
(seen from the motor side) in the total moment of inertia and
over one or more strokes see whether the ¨Inertial Match¨can be
achieved in combination with the available transmissions.
3) After 2) are all the working points of the motor inside the SOA? (Maximum
torque, maximum speed; this point is also called ¨Worst case operation
point¨).
4) Is Trms less than T100? Since T100 falls at elevated speeds
with e l e c t r o n i c a l l y
commutated motors, a safe design is obtained if the value of T100 at
the m a x i m u m s p e e d occurring in the design is compared
with Trms.
It is recommended that
the curve of the motor torque be drawn as a function of the transmission
ratio, because depending on motor moment of inertia, mechanical
time c o n s t a n t a n d required acceleration
for
example there can be a flat area around the optimum. Analysis
of the open loop transfer function of a servo system shows that
an advantage can be obtained by the selection of a certain ratio
between the moments of inertia of the motor and the load plus
retardation. Choosing equal ratio or simply deliberately a relatively
light motor also depends on the position of the sensors. The dissertation
by Mr. Groenguis (TU Eindhoven) goes into this more deeply.
Static/Dynamic Hybrid
In a similar fashion to the one described above a method can
be worked out that describes hybrids. It requires a good description
of the load. Since the quantity of calculations is considerable,
the use of a numerical tool is preferable, because a choice of
motor and transmission ratio must be determined iteratively. The
value of i that delivers a minimum torque is affected by the friction
and damping present, so the ¨inertial match¨ is not always the
best solution.
5For
more information vist. www.automotioninc.com